Kynn Generator KT27 – KT30S (1500 rpm) – 1 Phase powered by Kubota

Category:

Description

The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.

NOTES

  1. The applicable voltage range is 230V for 50Hz applications. For other voltages, please consult factory.
  2. This generating set is of fixed speed of 1500 rpm.
  3. KT27 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
  4. KT30S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data
Make & Model KUBOTA V3300-E2-BG2
Cylinders & Arrangement 4; vertical in-line
Bore & Stroke (mm) 98 x 110
Induction system Naturally aspirated
Combustion Indirect injection
Cycle 4 stroke
Compression ratio 22.6
Cooling System Water cooled
Displacement 3.318 liters
Lube oil capacity 13.2 liters Max
Coolant capacity 13.2 liters
Standard governor (Optional) Mechanical +/-5% (Electronic)
Engine Speed 1500 rpm
Fuel Consumption @ 100% Load 7.15 (L/H)
Fuel Consumption @ 75% Load 5.37 (L/H)
Fuel Consumption @ 50% Load 3.58 (L/H)
Fuel Consumption @ 25% Load 1.79 (L/H)
Radiator Cooling Air Flow (m3/s) 0.98
Emissions regulations EU Stage IIIA
Exhaust temperature ᵒC (max) 500
Max exhaust gas flow (m3/min) 6.63
Max. allowed back pressure (kPa) 7.1

The above performance data are valid as per the following specs:

  • Diesel Fuel is according to BS2869 Class A2 or equivalent.
  • Lubricating oil is according to Grade SAE 15W-40 API CI4.
  • The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data
Make & Model Leroy Somer TAL042F
Frequency / No. of poles 50Hz / 4P
Ingress protection IP23
Insulation class H
Terminals (Optional) 6 (12)
Excitation system SHUNT
Winding pitch 2/3
AVR model R120
Overspeed 2250 R.P.M.
Voltage regulation ± 1 %
Coolant air flow 0.1 m3/s

 Certification

  • The complete generating set is type-tested according to ISO 8528-8 standard.

 

Control Panel Specifications

GMP260MK (DSE6010 MKII) panel is an automatic start generating set panel of microprocessor-based design which is capable of interfacing with electronic engine through the can-bus J1939.  It is fully configurable by front fascia buttons and PC software as well. If Mains voltage is to be monitored, DSE6020MKII can be offered.

Circuit Breaker Schneider or ABB, 3 Pole MCB (4 Pole available as Optional)

Construction

Sheet Fabrication CNC shearing & bending
Paint type Heat-treated powder-coated
Paint application Electrostatic corona spraying
Durability tests §  IMPACT [EN ISO 6272]

§  Salt spray resistance [ASTM B117-73]

§  Humidity Resistance [ASTM D2247]

Compliance §  Panel is compliant with [ISO8528-8]

§  Clearance & Creepage [IEC60355-1]

§  Leakage current & Dielectric strength [IEC60355-1]

§  Protection against electric shock [IEC600 364-4-41]

Degree of protection IP55
Wire crimping §  Crimping force up to 20KN

§  Accuracy of 0.01mm

§  Each crimping is checked by Komax CFA+

Wire coding §  Wires are coded by wire color and cross-section

§  Wires are coded by printed numbers

§  Wires are coded by printed function of the wire

Certification

  • The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355

Genset Standard Features

 Assembly:

Gensets are assembled at Kynn Machinery Factory in compliance with ISO 8528 standard.

 Fabrication:

– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.

– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.

– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.

– The control panel enclosure is made up of reliable metal sheet.

Paint:

-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.

– Paints passed durability tests conforming to international quality standards.

– Impact (EN ISO 6272)

– Salt Spray Resistance (ASTM B117-73)

– Humidity Resistance (ASTM D2247)

Works-Testing:

– All Gensets are tested prior to dispatch.

– Test is automatically generated and checked according to ISO8528

– Test certificate is issued for each Genset

Equipment:

– Water cooled Radiator with belt driven blower fan and full guarding

– Electric starter with solenoid Relay

– Battery Charging Alternator

– Energized to run solenoid

– Replaceable fuel, oil and air filters

– Heavy duty leads acid battery with matching capacity (Amps & CCA)

– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.

– Integral Fuel Tank with 116 L capacity.

Documentation:

– User Manual for Operation, Installation and Maintenance guidance

– Wring Diagram.

– Test Report

– Maintenance Schedule

– Catalogues for Engine, Alternator & AVR

Genset Optional Features

Manual & Automatic Transfer Switches,

Synchronizing & Totalizing Panels

Fuel water separator

Water jacket heater

Oil heater

Fuel heater

Battery heater

Anti-condensation Heater

Air Shut-off Valve

Oil Sampler

Pre-lube Oil Pump