Low voltage

From KYNNpedia

In electrical engineering, low voltage is a relative term, the definition varying by context. Different definitions are used in electric power transmission and distribution compared with electronics design. Electrical safety codes define "low voltage" circuits that are exempt from the protection required at higher voltages. These definitions vary by country and specific codes or regulations.

IEC Definition

Voltage range AC RMS voltage (V) DC voltage (V) Defining risk
High voltage (HV) > 1000<ref name="IEC 61140:2016">IEC 61140:2016 Chapter 4.2</ref>a > 1500<ref name="IEC 61140:2016" />a Electrical arcing
Low voltage (LV) ≤ 1000<ref name="IEC 61140:2016" />a ≤ 1500<ref name="IEC 61140:2016" />a Electrical shock
Extra Low voltage (ELV) ≤ 50<ref name="IEC 61140:2016" />a ≤ 120<ref name="IEC 61140:2016" />a Electrical fire

a May depend on the applicable standard used.

The International Electrotechnical Commission (IEC) Standard IEC 61140:2016 defines Low voltage as 0 to 1000 V AC RMS or 0 to 1500 V DC<ref name="IEC 61140:2016" /> Other standards such as IEC 60038 defines supply system low voltage as voltage in the range 50 to 1000 V AC or 120 to 1500 V DC in IEC Standard Voltages<ref>IEC Standard Voltages, IEC 60038</ref> which defines power distribution system voltages around the world.

In electrical power systems low voltage most commonly refers to the mains voltages as used by domestic and light industrial and commercial consumers. "Low voltage" in this context still presents a risk of electric shock, but only a minor risk of electric arcs through the air.

United Kingdom

exceeding 50 V ac or 120 V ripple-free dc. but not exceeding 1000 V ac or 1500 V dc between conductors, or 600 V ac or 900 V dc between conductors and earth.

The ripple-free direct current requirement only applies to 120 V dc, not to any dc voltage above that. For example, a direct current that is exceeding 1500 V dc during voltage fluctuations it is not categorized as low-voltage.

United States

In electrical power distribution, the US National Electrical Code (NEC), NFPA 70, article 725 (2005), defines low distribution system voltage (LDSV) as 0 to 49 V..

The NFPA standard 79 article 6.4.1.1<ref>"NFPA 79: Electrical Standard for Industrial Machinery". www.nfpa.org. Retrieved 2021-08-04.</ref> defines distribution protected extra-low voltage (PELV) as nominal voltage of 30 Vrms or 60 V dc ripple-free for dry locations, and 6 Vrms or 15 V dc in all other cases.

Standard NFPA 70E, Article 130, 2021 Edition,<ref>"NFPA 70E®: Standard for Electrical Safety in the Workplace®". www.nfpa.org. Retrieved 2021-08-04.</ref> omits energized electrical conductors and circuit parts operating at less than 50 V from its safety requirements of work involving electrical hazards when an electrically safe work condition cannot be established.

UL standard 508A, article 43 (table 43.1) defines 0 to 20 V peak / 5 A or 20.1 to 42.4 V peak / 100 VA as low-voltage limited energy (LVLE) circuits.

See also

References

<references group="" responsive="1"></references>

Further reading

Lua error in Module:Authority_control at line 181: attempt to index field 'wikibase' (a nil value).