Voltage sag

From KYNNpedia

A voltage sag (U.S. English) or voltage dip<ref name=IEEE493>"IEEE 493-2007 - IEEE Recommended Practice for the Design of Reliable Industrial and Commercial Power Systems". The IEEE Standards Association. 2007-02-12. Retrieved 2018-01-09.</ref> (British English) is a short-duration reduction in the voltage of an electric power distribution system. It can be caused by high current demand such as inrush current (starting of electric motors, transformers, heaters, power supplies) or fault current (overload or short circuit) elsewhere on the system.<ref name=Bollen>Bollen, Math H.J. (1999). Solving power quality problems: voltage sags and interruptions. New York: IEEE Press. p. 139. ISBN 978-0-7803-4713-7.</ref>

Voltage sags are defined by their magnitude or depth, and duration.<ref name=Karady/> A voltage sag happens when the RMS voltage decreases between 10 and 90 percent of nominal voltage for one-half cycle to one minute.<ref name=Bollen/><ref name=UTS>"Industrial Voltage Regulator Power Conditioner". Utility Systems Technologies. Retrieved 25 September 2013.</ref> Some references define the duration of a sag for a period of 0.5 cycle to a few seconds,<ref name=Newnes/><ref name=Teodorescu>Remus Teodorescu; Marco Liserre; Pedro Rodríguez (2011). Grid Converters for Photovoltaic and Wind Power Systems. Wiley-IEEE Press. ISBN 978-1-119-95720-1.</ref> and a longer duration of low voltage would be called a "sustained sag".<ref name=Newnes>Vijayaraghavan, G, Mark Brown, and Malcolm Barnes (2004). Practical grounding, bonding, shielding and surge protection. Oxford: Newnes. p. 134. ISBN 978-0-08-048018-3.{{cite book}}: CS1 maint: multiple names: authors list (link)</ref> The definition of voltage sag can be found in IEEE 1159, 3.1.73 as "A variation of the RMS value of the voltage from nominal voltage for a time greater than 0.5 cycles of the power frequency but less than or equal to 1 minute. Usually further described using a modifier indicating the magnitude of a voltage variation (e.g. sag, swell, or interruption) and possibly a modifier indicating the duration of the variation (e.g., instantaneous, momentary, or temporary)."<ref name=Karady/>

Voltage sag in large power system

The main goal of the power system is to provide reliable and high-quality electricity for its customers. One of the main measures of power quality is the voltage magnitude. Therefore, Monitoring the power system to ensure its performance is one of the highest priorities.<ref>Association IS (2014) IEEE trial-use recommended practice for voltage sag and short interruption ride-through testing for end-use electrical equipment rated less than 1000V. Standard P1668-2014</ref> However, since power systems are usually grids including hundreds of buses, installing measuring instruments at every single busbar of the system is not cost-efficient. In this regard, various approaches have been suggested to estimate the voltage of different buses merely based on the measured voltage on a few buses.<ref name="Jalalat Liasi 2022 p. ">Jalalat, Hamed; Liasi, Sahand (2022-11-16). "Optimal location of voltage sags monitoring buses, based on the correlation rate between network buses with considering the probability distribution of variables". Electrical Engineering. Springer Science and Business Media LLC. 105: 509–518. doi:10.1007/s00202-022-01674-6. ISSN 0948-7921. S2CID 253619994.</ref>

Related concepts

The term "sag" should not be confused with a brownout, which is the reduction of voltage for minutes or hours.<ref>Standler, Ronald B. (1989). Protection of electronic circuits from overvoltages. New York: Wiley. p. 40. ISBN 9780471611219.</ref>

The term "transient", as used in power quality, is an umbrella term and can refer to sags, swells, dropouts, etc.<ref name="VedamSarma2008">R. Sastry Vedam; Mulukutla S. Sarma (2008). Power Quality: VAR Compensation in Power Systems. CRC Press. pp. 4–5 and 23. ISBN 978-1-4200-6482-7.</ref>

Swell

Voltage swell is the opposite of voltage sag. Voltage swell, which is a momentary increase in voltage, happens when a heavy load turns off in a power system.<ref name=Kazibwe>Kazibwe, Wilson E.; Sendaula, Musoke H. (1993). Electric power quality control techniques. New York: Van Nostrand Reinhold. p. 11. ISBN 978-0-442-01093-5.</ref>

Causes

Several factors can cause a voltage sag:

  • Some electric motors draw much more current when they are starting than when they are running at their rated speed.<ref name=Bollen/><ref name=Kazibwe/>
  • A line-to-ground fault will cause a voltage sag until the protective switchgear (fuse or circuit breaker) operates.<ref name=Bollen/><ref name=Kazibwe/>
  • Some accidents in power lines such as lightning or a falling object can cause a line-to-ground fault.<ref name=Kazibwe/>
  • Sudden load changes or excessive loads<ref name=Kazibwe/>
  • Depending on the transformer connections, transformers energizing<ref name=Teodorescu/>
  • Voltage sags can arrive from the power utility, but most are caused by local in-building equipment. In residential homes, voltage sags are sometimes seen when refrigerators, air-conditioners, or furnace fans start up.

Factors that affect the magnitude of sag caused by faults:

  • The distance between the victim and the fault source <ref name=Karady>Karady, George. "Effect of voltage sags on loads in a distribution system" (PDF).</ref>
  • The fault impedance<ref name=Karady/>
  • Type of fault<ref name=Karady/>
  • The voltage before the sag occurs<ref name=Karady/>
  • System configuration, e.g. system impedance and transformer connections<ref name=Karady/>